Earthing
Key: T = Terre (earth), N = neutral, C = combined, S = separate
TN-S
- Neutral connected to earth at supply only
- Max Ze 0.8Ω
TN-C-S
- Protective Multiple Earthing (PME)
- Supply neutral connected to earth at source and at intervals along the run
- Max Ze 0.35Ω
TT
- Installation has own earth electrode local to the install
- Distributor doesn’t provide an earth
TN-C
- Uncommon
- Requires exemption from Electrical Safety, Quality & Continuity Regulations
IT
- Uncommon
- Not permitted for Low Voltage public supply
- Source is not directly earthed